Performance Investigation and Optimization Studies on a Solar-Assisted Liquid Desiccant Air Conditioning System

dc.contributor.authorBhowmik, Mrinal
dc.date.accessioned2023-03-01T12:50:25Z
dc.date.accessioned2023-10-26T10:22:00Z
dc.date.available2023-03-01T12:50:25Z
dc.date.available2023-10-26T10:22:00Z
dc.date.issued2021
dc.descriptionSupervisors: Muthukumar, P and Anandalakshmi, Ren_US
dc.description.abstractLiquid desiccant dehumidification is a promising energy-extensive process for air dehumidification, which can easily be driven by any waste or renewable heat sources. In the current thesis, efforts are devoted to explore the thermo-kinetic properties of pure LiBr, CaCl2 as well as their mixtures through numerous material characterization techniques. Further, a thermal model for assessing the heat and mass transfer characteristics of the liquid desiccant dehumidifier/regenerator is developed based on the finite difference method. In order to assess the performance of the overall liquid desiccant system using a novel desiccant mixture, an experimental setup of solar-assisted liquid desiccant dehumidification has been fabricated, where solar evacuated tube collectors were used as a regeneration source to drive the liquid desiccant system in a close-loop. The overall energy balance between the ambient air and the liquid desiccant was estimated. Effects of independent parameters such as the solution to air flow rate, solution concentration and temperature on the dehumidifier-regenerator performance parameters such as latent heat ratio, condensation rate, desiccant mass fraction index, evaporation rate and latent and enthalpy effectiveness were analyzed. The results obtained from the present investigation showed that high solution to airflow (L/G) ratio enhanced the dehumidification and low L/G ratio enhanced the liquid desiccant regeneration rate. For tested liquid desiccant dehumidifier, condensation rate and latent effectiveness lie in the range of 2.2 to 5.6 g/m2-s and 36 to 68%, respectively. The evaporation rate, sensible and the latent effectiveness of the regenerator lies in the range of 0.1 – 11.2 g/m2-s, 25.9 – 63% and 10 – 92% depending on the operating conditions. The maximum latent heat ratio for the dehumidifier at the design condition was 0.62, and the thermal coefficient of performance of the system was found as 1.1. Further, the relationships between the performance parameters and control variables is developed through the application of various well-known artificial intelligence (AI) based methods such as artificial neural network (ANN), adaptive neuro-fuzzy inference system (ANFIS), and gene expression program (GEP). Subsequently, best AI model (GEP) based fuzzy logic is developed for optimizing dehumidifier/regenerator inlet process parameters in terms of multi-responsive performance characteristics using genetic algorithm. At a near-optimum point, the experimental results condensation rate (CR) of 5.584 g/m2-s, moisture effectiveness (ɛm) of 42% and latent heat ratio (LHR) of 0.83, respectively, were obtained. Lastly, an effort has been made to develop a novel liquid desiccant doped sodium carboxymethyl cellulose (NaCMC) films using citric acid as a crosslinker to explore the air dehumidification and regeneration capability of films.en_US
dc.identifier.otherROLL NO.166151103
dc.identifier.urihttp://172.17.1.107:4000/handle/123456789/2305
dc.language.isoenen_US
dc.relation.ispartofseriesTH-2864;
dc.subjectLiquid Desiccant Mixtureen_US
dc.subjectPacked Bed Dehumidifier/ Regeneratoren_US
dc.subjectSolar Collector Based Desiccant Regenerationen_US
dc.subjectHeat and Mass Transferen_US
dc.subjectArtificial Intelligent Modelsen_US
dc.subjectMulti-objective Optimizationen_US
dc.subjectNovel Desiccant Doped Hydrogel Filmsen_US
dc.titlePerformance Investigation and Optimization Studies on a Solar-Assisted Liquid Desiccant Air Conditioning Systemen_US
dc.typeThesisen_US
Files
Original bundle
Now showing 1 - 2 of 2
No Thumbnail Available
Name:
Abstract-TH-2864_166151103.pdf
Size:
185.02 KB
Format:
Adobe Portable Document Format
Description:
ABSTRACT
No Thumbnail Available
Name:
TH-2864_166151103.pdf
Size:
12.02 MB
Format:
Adobe Portable Document Format
Description:
THESIS
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Plain Text
Description: